CVE-2026-11826

HIGH
Published Jul 18, 2026 Modified Jul 20, 2026 CWE-122

Description

OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.

Is your site exposed to CVE-2026-11826?

Run a free security scan — no signup, results in seconds.

CVSS v3.1 Score

8.8
HIGH
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

EPSS — Exploit Prediction

0.0042
Probability of exploitation
0.34%
Percentile rank

EPSS estimates the probability that this vulnerability will be exploited in the wild within the next 30 days. A higher score means more likely to be exploited.

Weakness Type (CWE)

CWE-122 CWE-122

References

Frequently Asked Questions

What is CVE-2026-11826? +
OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4. It has a CVSS v3.1 base score of 8.8 (HIGH).
How severe is CVE-2026-11826? +
CVE-2026-11826 has a CVSS v3.1 score of 8.8 out of 10, rated HIGH. This is a high-severity vulnerability that should be prioritized for patching. The EPSS score is 0.0042, placing it in the 0th percentile for exploitation probability.
How do I check if I'm vulnerable to CVE-2026-11826? +
You can use Secably's free Website Scanner to check your website for known vulnerabilities. For infrastructure scanning, use the Port Scanner to identify exposed services that may be affected. Check the vendor advisories linked above for specific patch and version information.